CJ19(CJ16)Series
AC Contactor |
|
|
|
|
|
|
Application
The contactor is suitable for using in the circuits up to
voltage 380V AC 50Hz for putting the low voltage reactive power compensation
device or cutting low voltage shunted capacitor. The contactor is supplied
with the suppressing in rush current shock to capacitor while closing
and suppressing
over-voltage while breaking.
|
|
|
|
|
|
|
Rated current
|
Auxiliary contact
|
Number
|
25 32 43
|
20E
02E
11E
|
2NO
2NC
NO+2NC
|
63
|
21E
12E
|
2NO+NC
NO+2NC
|
|
|
|
|
|
|
|
|
|
Model
|
CJ19-25
|
CJ19-32
|
CJ19-43
|
CJ19-63
|
Electrical endurance(ops)
|
105
|
Rated current Ie(400v capacitor)
|
17.3
|
26
|
29
|
43
|
Rated insulation(V)
|
750
|
Coil power loss(cold coil
1.0us,50Hz)starting closing
|
68/12VA
|
Coil operating range
|
(0.85-1.1)Us
|
Short circuit protection
|
1.5-2.5Ie 16A
|
Energy for suppressing inrush
current to capacitor
|
20Ie
|
Rated operating current of
auxiliary(when 380V)(A)
|
6
|
4
|
Rated capacity(400V)KVar
|
12
|
18
|
20
|
30
|
We can supply the contactor
which controlling coil is24 36 48 110 127 220 380 415 550
600as client require
|
|
|
|
|
|
|